67
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
146 XDCR TYPE
The type of transducer connected
to the Transducer Port
Mode Value
0 UINT16 R/W
BK 422 0
mV/V 1
Rao 2
1-5V 3
4-20mA 4
147
PERMISSIVE
INPUT MODE
Whether the PERMISSIVE output is
normally open or normally closed
when inacve.
Mode Value
1 INT16 R/WN.C. 1
N.O. 0
148
PS1 INPUT
MODE
Whether the PS1 output is
normally open or normally closed
when inacve.
Mode Value
0 INT16 R/WN.C. 1
N.O. 0
149
PS2 INPUT
MODE
Whether the PS2 output is
normally open or normally closed
when inacve.
Mode Value
0 UINT16 R/WN.C. 1
N.O. 0
150
PROOF OF
CLOSURE
INPUT MODE
Whether the PROOF OF CLOSURE
output is normally open or
normally closed when inacve.
Mode Value
1 UINT16 R/WN.C. 1
N.O. 0
151 - 154 UNUSED Unused N/A R
155 PASSCODE
Passcode required to access the
Sengs menu and Diagnosc Info
menu
Range Value
0000 INT16 R/WMin 0000
Max 9999
156
PASSCODE
ENABLE
Enable or disable the Sengs
menu and Diagnosc Info menu
passcode
Mode Value
0 INT16 R/WEnabled 1
Disabled 0
157 - 159 UNUSED Unused
N/A R
160
DISPLAY
TIMEOUT
The amount of me in seconds that
the display will remain on aer the
last menu interacon
Range Value
1800 INT16 R/WMin 30
Max 1800