i--H, Active alarm when the current is higher than the alarm value.
F--L, Active alarm when the frequency is less than the alarm value.
i--L, Active alarm when the current is less than the alarm value.
di1H, Active alarm when digital input 1 is connected.
di2H,Active alarm when digital input 2 is connected.
di1L, Active alarm when digital input 1 is disconnected.
di2L,Active alarm when digital input 2 is disconnected.
To validate the data, press the key.
Use the and keys to browse the conguration screens of the menu.
5�4�4�- CONNECTION DELAY
This screen is used to congure the alarm connection delay.
dELy
0010
Use the , key to modify the value of the ashing digit
When the desired value is shown on the screen, press the key to skip the digit.
Minimum conguration value: 0 x 0.1 s
Maximum conguration value: 9999 x 0.1 s
Example: Use program 0050 to congure a value of 5 s.
To validate the data, press the key.
Use the and keys to browse the conguration screens of the menu.
5�4�5�- ALARM VALUE
The value after which the alarm will be activated is congured on this screen.
uALE
000.0
Use the , key to modify the value of the ashing digit
When the desired value is shown on the screen, press the key to skip the digit.
Minimum conguration value: 0
Maximum conguration value: 9999
27
Instruction Manual
DHC-96 Aac