Full Redundancy
Mode
Input Source
Redundancy Mode
Power Supply
Redundancy Mode
Combined Mode
—1200 W—4200 W1 power supply
2400 W2400 W4200 W8400 W2 power supplies
3600 W3600 W8400 W12,600 W3 power supplies
4800 W4800 S12,600 W16,800 W4 power supplies
110-V and 110-V inputs
—1200 W—2400 W1 power supply
2400 W2400 W2400 W4800 W2 power supplies
3600 W3600 W4800 W7200 W3 power supplies
4800 W4800 W7200 W9600 W4 power supplies
Single input per power supply
220-V input
———3000 W1 power supply
——3000 W6000 W2 power supplies
——6000 W9000 W3 power supplies
——9000 W12,000 W4 power supplies
110-V input
———1200 W1 power supply
——1200 W2400 W2 power supplies
——2400 W3600 W3 power supplies
——3600 W4800 W4 power supplies
11
The Cisco Nexus 7018 switch uses up to four 6-kW power supplies, the Cisco Nexus 7010 switch uses
up to three 6-kW power supplies, and the Cisco Nexus 7009 uses up to two 6-kW power supplies.
Table 22: Power Availability for 7.5-kW AC Power Supplies
Full Redundancy
Mode
Input Source
Redundancy Mode
Power Supply
Redundancy Mode
Combined Mode
Dual inputs per power supply
220-V and 220-V inputs
—3750 W—7500 W1 power supply
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
159
Technical Specifications
Power Supply Configuration Modes