MaximumTypicalQuantityComponent
——
1 to 8Line cards supported by N9K-C9508-FM-S fabric modules
594 W440 W32-port 100-Gigabit Ethernet QSFP28 line card
(N9K-X9432C-S)
–
———
Fabric modules
251 W176 W
—
3
4
40-Gigabit N9K-C9508-FM fabric modules
- Supporting N9K-X95xx line cards
- Supporting N9K-X94xx line cards
–
650 W455 W4100-Gigabit N9K-C9508-FM-E fabric modules supporting -EX
line cards
–
250 W240 W
—
6
5 (plus 1
for
redundancy)
100-Gigabit N9K-C9508-FM-R fabric modules
- Supporting N9K-X9636C-RX line cards
- Supporting N9K-X9636C-R and N9K-X9636Q-R line cards
–
450 W340 W4100-Gigabit N9K-C9508-FM-S fabric modules supporting -S
line cards
–
250 W176 W3Fan trays (N9K-C9508-FAN)
Maximum Power Available to the Switch
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of
power supplies, and the mode used.
Cisco Nexus 9508 NX-OS Mode Switch Hardware Installation Guide
119
System Specifications
Maximum Power Available to the Switch