Cisco Nexus 9508 - Installing a Chassis in a Rack or Cabinet

Cisco Nexus 9508
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M6 x 19-mm (or 12-24 x 3/4 in.) Phillips screws (at
least 6 per rail)
2Adjustable bottom-support rails (2)1
Use at least three screws on each end of each bottom-support
rail.
Note
Step 3
Repeat Steps 1 and 2 to attach the other bottom-support rail to the rack.
Make sure that the two bottom-support rails are level with one another. If they are not level, adjust the higher
rail down to the level of the lower rail.
Note
What to Do Next
When the bottom-support rails are installed at the lowest possible RU and are level, you are ready to install
the chassis in the rack or cabinet.
Installing a Chassis in a Rack or Cabinet
Before You Begin
Verify that the chassis shipment is complete and undamaged.
Verify that a four-post rack or cabinet is installed and secured to the concrete subfloor.
Statement 1048Rack Stabilization
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be
bolted to the floor before you slide the unit out for servicing. Failure to stabilize the
rack can cause the rack to tip over.
Warning
Verify that the bottom-support rails have been attached to the lowest possible RU in the rack or cabinet
and there is 13 RU (22.7 in [57.8 cm]) of space above the rails to install the chassis.
Cisco Nexus 9508 NX-OS Mode Switch Hardware Installation Guide
26
Installing a Chassis
Installing a Chassis in a Rack or Cabinet