Step 19 Align the screw holes on the left top air deflector with the screw holes on the left side of the chassis.
Step 20 Insert M4 pan-head screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 21 Place the mounting bracket flush in the middle position on the left top air deflector (see Diagram 4 ofFigure
38: Mounting the Bracket with Air Deflectors (Front-to-Top) on the ONS 15454 M6 Shelf for ETSI Rack
Configuration - Middle Position , on page 42).
Step 22 Align the screw holes on the mounting bracket with the screw holes on the left top air deflector.
Step 23 Insert M4 flat-head screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Figure 38: Mounting the Bracket with Air Deflectors (Front-to-Top) on the ONS 15454 M6 Shelf for ETSI Rack Configuration - Middle
Position
Step 24 Return to your originating procedure. (NTP).
Installing the ONS 15454 M6 Shelf
42
Installing the ONS 15454 M6 Shelf
DLP-G565 Mounting the Bracket with Air Deflectors (Front-to-Top) on the ONS 15454 M6 Shelf for ETSI Rack Configuration