8.
Specifications
Span Fully selectable in terms of dust,
opacity, Ringelmann or extinction
Response Time Selectable from 10 seconds to 30 day
rolling average
Maximum Path Length 6 metres
Construction Fully sealed to IP65
Ambient temperature limits Transmitter and Receiver
-20
o
C to +80
o
C
PSU/SPU
20
o
C to +70
o
C
Analogue Outputs 0 or 4 - 20mA linear, 500 max.
Contact Outputs High Opacity/Dust alarm
Data valid
Both rated at 1A @ 30V DC, 0.3A
@ 120V AC, max. power resistive
load 30W
Keypad Inputs Oxygen
Temperature
Pressure
Water Vapour
Analogue Inputs Oxygen 4 - 20mA
(Optional input PCB Temperature 4 20mA
required Model 1001) Pressure 4 - 20mA
Water Vapour 4 - 20mA
Plant Status Optional
Dust Calibration By independent analysis (by others)*
Accuracy 0.2% Opacity (with auto zero active)
1.0% Opacity (without auto zero)