To aid commissioning, and to record any subsequent changes to the operating
parameters, the table at 3.7.3. Example 2 : Dust Monitor, displays all the
options available and can be used as a record. Two example set-ups are also
shown in this table. (Details at the end of this section).
Setting Parameters after Initial Calibration
This is a step by step, keystroke by keystroke description of setting the
parameters in the signal processor. All definitions of parameters are given in the
operation section. It is strongly recommended that the operation details are
read, and all required parameters for the process in hand determined before
entry into the signal processor. The table at 3.7.3. Example 2 : Dust Monitor can
be used to make a note of which parameter settings are to be used.
1. Press MODE until SET UP is displayed in the top left of the LCD
(4 times).
2. Press ENTER (4 times). The security code has not yet been set,
so it is still at the default factory setting of 0000. When the code
has been set, after this section has been completed the 4 digit
security code must be entered.
3. The first sub menu is AVERAGES.
4. Press ENTER to access this menu and the first option is seconds.
5. Press ENTER to access the values. Use the UP and DOWN arrow
keys to select the average required. These can be chosen from 10
to 60 seconds in 10-second intervals.
6. When the required value is displayed press ENTER. The value
has now been entered into memory.
7. The menu will automatically scroll down to the next option, which
is the minutes average (minutes).
8. Press ENTER to access values for this average. It is set in the
same way as for seconds.
! Remember that when ENTER is pressed after a value has been