CODEL
OPS. 141 18
Issue : A
Revision : 1
Date : 14/06/18
Doc i/d : 0141/6
050028
9. Ranges for the averages are :
minute 01 to 60 in 1 minute intervals
hour 01 to 24 in 1 hour intervals
day 01 to 30 in 1 day intervals
10.When days has been entered the LCD will read RESET, select
YES and the display will prompt SURE. Select YES and after the
averages are reset the display will read EXIT. Press ENTER and
the processor will return to the SET UP mode menu option
AVERAGES.
11.Use DOWN arrow to show CONFIGURE O/P 1 (configure output
1). Press ENTER to access the menu. The first option is Output.
12.Press ENTER to access this option and use the UP and DOWN
arrow keys to select either 0 or 4mA as the origin for current at the
outputs. Press ENTER when the correct one has been selected.
13.The OUTPUT option is exited and the AVERAGES option is
selected. Press ENTER to access the option and use UP and
DOWN keys to select which average is to be displayed in the
operating mode.
14.Press ENTER and Units is the next option. Press ENTER to
access the option and use the UP and DOWN keys to select which
units are displayed. The choices are:
%OP
Optical Density
mg/m
3
mg/Nm
3
Ringelmann
15.Press ENTER and Span is displayed. Press ENTER and select
the span value required.
16.The first digit is selected by using the UP and DOWN arrow keys
and pressing ENTER, the cursor then moves to the second and
third digits in turn.
17.When all have been selected press ENTER.
18.The Span menu is exited and Fault Cond (condition) is viewed.
19.Press ENTER and select either :

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CODEL EnergyTech 100 Series and is the answer not in the manual?

CODEL EnergyTech 100 Series Specifications

General IconGeneral
BrandCODEL
ModelEnergyTech 100 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals