NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
144
12.2.6.7 Setpoint: BusLeft >V
Group
BusL protect
Range [units]
BusLeft <V .. 150 [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts threshold for busL overvoltage protection.
NOTE:
This protection is History record type - for more information on protection
types please refer to alarm types section.
NOTE:
It is possible to disable this protection through setpoint BusLVolt prot.
12.2.6.8 Setpoint: BusLeft <V
Group
BusL protect
Range [units]
50 .. BusLeft >V [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts threshold for busL undervoltage protection.
NOTE:
This protection is History record type - for more information on protection
types please refer to alarm types section.
NOTE:
It is possible to disable this protection through setpoint BusLVolt prot.
12.2.6.9 Setpoint: BusLeft V del
Group
BusL protect
Range [units]
0.00 .. 600.00 [s]