reserves in the chapter Reserves, minimal running power. 
The currently active reserve set is selected by binary inputs Load res 2, Load 
res 3 and Load res 4. If none of these inputs is active the set #1 is selected. 
NOTE:  
The reserve for stop must be always adjusted higher than the reserve for 
start. 
 
NOTE:  
# sign in the name of this setpoint marks that this setpoint is shared among 
all controllers connected by CAN2 bus.  
 
 
12.2.8.16  Setpoint: #%LdResStrt 2 
This setpoint is used to adjust the load reserve for start in relative mode. i.e. 
Pwr mgmt mode = REL (%) if the reserve set #2 is active. Learn more about 
reserves in the chapter Reserves, minimal running power. 
The currently active reserve set is selected by binary inputs Load res 2, Load 
res 3 and Load res 4. If none of these inputs is active the set #1 is selected. 
NOTE:  
If the relative power management is selected, this setpoint (or the setpoints 
%LdResStrt 1, %LdResStrt 3 or %LdResStrt 4 depending on which load 
reserve set is selected) determines also the number of gensets (that are part 
of the power management) which will start (according to their priority and 
nominal power).  
 
NOTE:  
# sign in the name of this setpoint marks that this setpoint is shared among 
all controllers connected by CAN2 bus.  
 
 
12.2.8.17  Setpoint: #%LdResStop 2