InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
12.2.8.28 Setpoint: #MinRunPower 3
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated
by the input MinRun power 3 which is in MINT application (in InteliMains it is
for compatibility purposes only).
NOTE:
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.29 Setpoint: #RunHrsMaxDiff
This setpoint adjusts the "deadband" for the running hours equalization
function. The priorities are swapped not until the relative engine hours (RHE)
difference is higher than this deadband.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.30 Setpoint: #PwrBandContr 1
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]