InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
This value shows the sum of nominal powers of all gensets that are available 
for power management (in any state - stopped, running etc.). See also values 
TotRunPnomAll and TotRunPnom. This value is active only when BTB is 
closed. 
For more information on power management please refer to the chapter 
Power management. 
 
13.1.5.2  Value: TotRunPnom 
This value shows the sum of nominal powers of all running gensets that are 
participating in power management. See also values TotRunPnomAll and 
TotAvlbPnom. This value is active only when BTB is closed. 
For more information on power management please refer to the chapter 
Power management. 
 
13.1.5.3  Value: Act Reserve 
Actual absolute reserve. This value is active only when BTB is closed. In BTB, 
it can be used in two-level load shedding.  
 
13.1.5.4  Value: LoadRes Start 
If the actual absolute reserve is lower than this value the next gen-set which 
is about to be started in power managament is started. This value is the 
exact copy of setpoint #LoadResStrt X.