InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
239
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller receives messages from the
controller which has address corresponding with the bit position. Bit 0
represents address 1 etc. This value contains information about controllers
with addresses 1-16.
NOTE:
The bit which corresponds to the own controller is always set to "1".
13.1.12.7 Value: CAN32
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller receives messages from the
controller which has address corresponding with the bit position. Bit 0
represents address 17 etc. This value contains information about controllers
with addresses 17-32.
NOTE:
The bit which corresponds to the own controller is always set to "1".
13.1.12.8 Value: Reg16
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position plays active role in the power management. Bit 0
represents address 1 etc. This value contains information about controllers
with addresses 1-16.
13.1.12.9 Value: Reg32
Group
Info
Units
-