InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
270
comparison to the up and down inputs, which does. However, if the reset
input is active, the remotely written data are not accepted.
14.2.1.57 Binary input: ExtValue3reset
Related FW
3.0
Description
The ExtValue 3 is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint ExtValue3deflt.
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the ExtValue command.
NOTE:
Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset
input is active, the remotely written data are not accepted.
14.2.1.58 Binary input: ExtValue4reset
Related FW
3.0
Description
The ExtValue 4 is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint ExtValue4deflt.
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the ExtValue command.
NOTE:
Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset
input is active, the remotely written data are not accepted.
14.2.1.59 Binary input: IssueActCallC1
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the