ID-FLX Lite & Telecom Global Guide
138
Comm object 8260 Related applications
Description
Limit for Warning Underspeed protection. Active protection is indicated as Wrn Underspeed in Alarm list.
Under speed Warning protection is inactive 5 s after RPM is over Starting RPM (page 111) and during the
Idle time.
The READY TO LOAD (PAGE 201) is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 5 -
Step 1
Comm object 12620 Related applications
Description
Engine is switched to Cooling state when Binary input FlowSwitch is not closed within Flow SwitchDel after
Running(Ready to load) engine state activation.
Flow SwitchDel
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] DISABLED, ENABLED [-]
Default value -
Step -
UnderspeedSd

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals