Comm object 8260 Related applications
Description
Limit for Warning Underspeed protection. Active protection is indicated as “Wrn Underspeed” in Alarm list.
Under speed Warning protection is inactive 5 s after RPM is over Starting RPM (page 111) and during the
Idle time.
The READY TO LOAD (PAGE 201) is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 5 -
Step 1
Comm object 12620 Related applications
Description
Engine is switched to Cooling state when Binary input FlowSwitch is not closed within Flow SwitchDel after
„Running“(Ready to load) engine state activation.
Flow SwitchDel
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] DISABLED, ENABLED [-]
Default value -
Step -
UnderspeedSd