ID-FLX Lite & Telecom Global Guide
207
Related FW 2.5.0 Related applications
Comm object 422
Description
Output closes if the ServiceTime alarm activates. Service time is adjusted by setpoint NextServTime (page
156).
The output opens, if
Alarm is not active and
FAULT RESET is pressed
ServiceTime
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1161
Description
Output closes if the value DEF Tank Level drops under 10%, this level is adjustable in DEF Level Min
(page 163).
Outup opens if the value DEF Tank Level exceeds 90%. This upper limit is adjusted inDEF Level Max
(page 163).
Note: This output is working only under condition ECU is configured and engine is in running state.
DEF Tank Level
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 527
Description
In case the binary input is configured to any control function, the binary output depicts the state of the binary
input. BI1, BI2, BI3, BI4, BI5, BI6 are assigned for controller, binary inputs, BI7, BI8, BI9, BI10 are assigned
for IL-NT IO1 optional card.
BI1 - stat
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 528
Description
In case the binary input is configured to any control function, the binary output depicts the state of the binary
input. BI1, BI2, BI3, BI4, BI5, BI6 are assigned for controller, binary inputs, BI7, BI8, BI9, BI10 are assigned
for IL-NT IO1 optional card.
BI2 - stat
6 back to List of LBO