EasyManuals Logo

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #142 background imageLoading...
Page #142 background image
ID-FLX Lite & Telecom Global Guide
142
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 10 -
Step 1
Comm object 8377 Related applications
Description
Delay for ANALOG INPUT 3.
Note: Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input
with range 0-2500 Ω.
AIN3 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] Batt undervolt (page 142) .. 40.0 [V]
Default value 36.0 -
Step 0.1
Comm object 9587 Related applications
Description
High battery voltage Warning limit.
Batt overvolt
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 80.0 .. Batt overvolt (page 142) [-]
Default value 18.0 -
Step 0.1
Comm object 8387 Related applications
Description
Low battery voltage Warning limit.
Batt undervolt
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 5 -
Step 1
Comm object 8383 Related applications
Description
Delay for low and high battery voltage alarm.
Batt volt del
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals