ID-FLX Lite & Telecom Global Guide
142
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 10 -
Step 1
Comm object 8377 Related applications
Description
Delay for ANALOG INPUT 3.
Note: Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input
with range 0-2500 Ω.
AIN3 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] Batt undervolt (page 142) .. 40.0 [V]
Default value 36.0 -
Step 0.1
Comm object 9587 Related applications
Description
High battery voltage Warning limit.
Batt overvolt
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 80.0 .. Batt overvolt (page 142) [-]
Default value 18.0 -
Step 0.1
Comm object 8387 Related applications
Description
Low battery voltage Warning limit.
Batt undervolt
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 5 -
Step 1
Comm object 8383 Related applications
Description
Delay for low and high battery voltage alarm.
Batt volt del
6 back to List of setpoints