ID-FLX Lite & Telecom Global Guide
141
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [°C]
Default value 90 -
Step 1
Comm object 8376 Related applications
Description
Shutdown limit level for ANALOG INPUT 2.
AIN2 Level 2
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 5 -
Step 1
Comm object 8371 Related applications
Description
Delay for ANALOG INPUT 2 alarm.
Note: Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type
of input with range 0-2500 Ω.
AIN2 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. +10000 [%]
Default value 20 -
Step 1
Comm object 8381 Related applications
Description
Warning limit level for ANALOG INPUT 3.
AIN3 Level 1
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [%]
Default value 10 -
Step 10
Comm object 8382 Related applications
Description
Shutdown limit level for ANALOG INPUT 3.
AIN3 Level 2
6 back to List of setpoints