EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #141 background imageLoading...
Page #141 background image
ID-FLX Lite & Telecom Global Guide
141
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [°C]
Default value 90 -
Step 1
Comm object 8376 Related applications
Description
Shutdown limit level for ANALOG INPUT 2.
AIN2 Level 2
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 5 -
Step 1
Comm object 8371 Related applications
Description
Delay for ANALOG INPUT 2 alarm.
Note: Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type
of input with range 0-2500 Ω.
AIN2 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. +10000 [%]
Default value 20 -
Step 1
Comm object 8381 Related applications
Description
Warning limit level for ANALOG INPUT 3.
AIN3 Level 1
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [%]
Default value 10 -
Step 10
Comm object 8382 Related applications
Description
Shutdown limit level for ANALOG INPUT 3.
AIN3 Level 2
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals