ID-FLX Lite & Telecom Global Guide
200
Related FW 2.5.0 Related applications
Comm object 1247
Description
Output closes together with Prestart time (page 112) and opens after the engine is stopped.
Stopped engine conditions: RPM = 0, Starting POil (page 111), D+ function (page 119) (if enabled).
Air valves
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 2
Description
The output closes if:
Any warning, cooldown or shutdown comes up or
The engine malfunctions
The output opens if
FAULT RESET is pressed
The output closes again if a new fault comes up.
Alarm
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1
Description
The output closes if:
Any warning or shutdown comes up or
The engine malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of LBO HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Horn
6 back to List of LBO