EasyManua.ls Logo

ComAp InteliDrive Lite

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID-FLX Lite & Telecom Global Guide
216
Related FW 2.5.0 Related applications
Comm object 436
Description
Output activates when Timer1 is active. Simultaneously the engine is started when is in AUT mode.
Timer1
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 437
Description
Output activates when Timer2 is active. Simultaneously the engine is started when is in AUT mode.
Timer2
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1252
Description
The output closes prior to the engine start (Prestart) and opens when Starting RPM (page 111) speed is
reached. During repeated crank attempts the output is opened.
Glow plugs
6 back to List of LBO

Table of Contents

Other manuals for ComAp InteliDrive Lite

Related product manuals