ID-FLX Lite & Telecom Global Guide
201
Related FW 2.5.0 Related applications
Comm object 62
Description
The output is closed if following conditions are fulfilled:
Engine is not running and
No Shut down or Slow stop alarm is active
Controller is not in OFF mode
Ready
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 58
Description
The output is closed if engine is running and no alarm is active it is possible to close load. The output opens
when Wrn Underspeed protection is active and during cooling state.
Ready to load
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 67
Description
Output closes if the engine is in Running state.
Running
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 74
Description
The output closes when engine is in Cooling state.
Cooling
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 592
Description
One second pulse as echo for panel Fault reset button.
Fault Reset
6 back to List of LBO

Table of Contents

Other manuals for ComAp InteliDrive Lite

Related product manuals