ID-FLX Lite & Telecom Global Guide
199
Related FW 2.5.0 Related applications
Comm object 36
Description
The output closes prior to the engine start (Prestart) and opens when Starting RPM (page 111) speed is
reached. During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Prestart
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 574
Description
The output closes prior to the engine start and opens when Starting RPM (page 111) speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow or pre-heat.
Preglow
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 40
Description
The output closes when engine starts and opens after AfterCool time (page 116) after stop of the engine.
Cooling pump
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object
Description
The output either follows the Nominal/Idle binary input or I/O button in MAN mode or follows the engine state
in AUT mode:
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to countdown
when Start speed reached. The Underspeed (page 137) is not evaluated during idle time. Start fail
protection occurs if the RPM drop below 2RPM during idle state.
Note: When LBI NOMINAL/IDLE (PAGE 189) is configured (to a physical binary input), it has priority and
the switching between the nominal and the idle speed by I/0 button is blocked.
Idle/Nominal
6 back to List of LBO