ID-FLX Lite & Telecom Global Guide
119
Setpoint group Engine parameters Related FW 2.5.0
Range [units] ENABLED, CHRGFAIL, DISABLED [-]
Default value DISABLED -
Step -
Comm object 9683 Related applications
Description
ENABLED
The D+ terminal is used for both functions - “running engine” detection and charge
fail detection.
CHRGFAIL The D+ terminal is used for charge fail detection only.
DISABLED The D+ terminal is not used. Default state.
Note: The magnetization current is provided independently on this setpoint value.
The D+ charge fail protection becomes active after Idle time (page 115) reaches zero.
D+ function
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] ENABLED, DISABLED [-]
Default value ENABLED -
Step -
Comm object 11086 Related applications
Description
The setpoint enables adjustment of the electronic engine control by following settings.
ENABLED
There is a full available control of an electronic engine given by the setting of the
ECU unit of the engine, i.e. Start request, Stop request, Speed request are enabled
if available. Default state.
DISABLED
Control of an electronic engine is fully blocked and the ID-Lite can only monitor the
values of an electronic engine.
ECU Control
6 back to List of setpoints