Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 10 -
Step 1
Comm object 9270 Related applications
Description
Delay for Wrn/Sd AIN9 alarm.
Note: Analog input 9 is configurable with basic two levels protection and it is voltage type of input with
range 0-10îV.
AIN9 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 65535 [h]
Default value 10000 YES
Step 1
Comm object 9648 Related applications
Description
Counting down when engine is running, from the moment of setting up the value of working hours in
LiteEdit/controller. This value is counting and changing in LiteEdit/controller as well. Service time alarm
appears if reaches zero, until non-zero value is set.
Note: Set the NextServTime = 65535îh to disable count down. The setpoint stays constant, but
Statistics value (visible in LiteEdit) displays #### invalid value.
NextServTime
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0.0 .. 5.0 [RPM]
Default value 0.0 -
Step 0.1
GearBoxRatio