ID-FLX Lite & Telecom Global Guide
163
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 0 -
Step 1
Comm object 13084 Related applications
Description
Seven setpoints are dedicated for separately adjustment of the delay for each of binary inputs according to
the Class B protection standard.
Note: The corresponding BIN protection has to be configured as Running only in LiteEdit.
BIN7 Prot Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 150 [%]
Default value 10 -
Step 1
Comm object 13178 Related applications
Description
Diesel Exhaust Fluid level protection activates DEF TANK LEVEL (PAGE 207) when received level (J1939 -
SCR - Selective Catalytic Reduction message) is below DEF Level Min for more than (fix) 3s delay. This
function is active for IVECO NEF&&Cursor engine. LBO can be active for running engine only.
DEF Level Min
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 150 [%]
Default value 90 -
Step 1
Comm object 13379 Related applications
Description
Diesel Exhaust Fluid level protection deactivates DEF TANK LEVEL (PAGE 207) when received level (J1939
- SCR - Selective Catalytic Reduction message) is above DEF Level Max for more than (fix) 3s delay. This
function is active for IVECO NEF&&Cursor engine.
Note: DEF Level is usual signage of Urea tank level, which is more often used in United States.
DEF Level Max
6 back to List of setpoints