InteliMains 210 Global Guide
106
Terminal
Event
SMS
Warning
SMS
BOC
SMS
Shutdown
SMS
Event
email
Warning
email
BOC
email
Shutdown
email
CM-RS232-485 no no no no no no no no
CM-Ethernet no no no no yes yes yes yes
CM-GPRS yes yes yes yes
no
yes*
yes*
no
yes*yes*
no
yes*
yes*
noyes*yes*
CM-4G-GPS yes yes yes yes
no
yes*
yes*
no
yes*yes*
no
yes*
yes*
noyes*yes*
Note: * Only with enabled Mode (page 274).
Note: * Only with enabled Mode (page 274).
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a
new alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms on binary or analog inputs
Controller built-in alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC,
Stp, MP, MPR). Then the alarm name follows. In some cases the prefix can be omitted.
User configured alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC,
MP, MPR). Alarm type is selected by user during the configuration of binary or analog input as alarm. Then the
alarm name follows. Name is adjusted by user during the configuration of binary or analog input as alarm.
Built-in alarms
Events
specification
Protection
type
Description
Wrn Battery Voltage WRN
Battery voltage is out of limits given by Battery Undervoltage (page
180) and Battery Overvoltage (page 180) setpoints.
Binary input Configurable Warning/MP/MPR alarms on the binary inputs.
RTC Battery Flat WRN RTC battery weak or flat and has to be changed.
Parameters Fail NONE
Wrong check-sum of parameters. Happens typically after downloading
new firmware or changing of the parameter. The controller stays in
INIT mode. Check all parameters, change value of at least one
parameter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals