Subgroup: Transferred Bus Power Measurement
Setpoint group Process Control Related FW 2.0.0
Range [units] None/Mains CT/Analog Input [-]
Default value Mains CT Alternative config NO
Step [-]
Comm object 10599 Related applications MCB, MGCB, BTB
Description
Defines source value of the Bus Left Import (page 367) measurement.
None The Transferred Bus Power is not measured.
Bus CT
The Bus Left Import (page 367) value is measured via Bus CTs.
Analog Input
The Bus Left Import (page 367) value is measured via analog input, accordingly LAI:
BUS IMPORT MEASUREMENT (PAGE 490).
Bus Power Measurement
6 back to List of setpoints
Subgroup: BTB Control
Setpoint group
Process
Control
Related FW 2.0.0
Range [units] Enabled / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 16047 Related applications BTB
Description
Setpoint for adjustment of the direction of synchronization. This setpoint has to be Enable for situations
where the Mains is on the left side and gen-sets are on the right side.
Note: In case the Mains is on the right side, the controller will not try to synchronize.
Synchronization R To Mains