InteliMains 210 Global Guide
193
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 600 [-]
Default value 5 Alternative config NO
Step 1
Comm object 8549 Related applications MCB, MGCB
Description
This setpoint adjusts the delay of the system activation after the binary input REMOTE START/STOP (PAGE
433) has been activated.
#System Start Delay
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 600 [-]
Default value 30 Alternative config NO
Step 1
Comm object 8550 Related applications MCB, MGCB
Description
This setpoint adjusts the delay of the system deactivation after the binary input REMOTE START/STOP (PAGE
433) has been deactivated.
#System Stop Delay
6 back to List of setpoints
Subgroup: Load Reserve Set 1
Setpoint group Power Management Related FW 2.0.0
Range [units]
0 .. #Stopping Load Reserve 1 (page 194) [kW]
Default value 60 kW Alternative config NO
Step 1 kW
Comm object 8489 Related applications MCB, MGCB
Description
This setpoint is used to adjust the load reserve for start of next gen-set in absolute mode. i.e. #Power
Management Mode (page 192) = ABS.
IMPORTANT: Logical binary input LOAD RES 2 ACTIVE (PAGE 430) has to be deactivated,
otherwise setpoints of Load Reserve Set 2 are used.
Note: See Power management (page 78) chapter for more information.
#Starting Load Reserve 1
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals