InteliMains 210 Global Guide
196
Setpoint group Power Management Related FW 2.0.0
Range [units]
#Starting Load Reserve 2 (page 195) .. 32 000 [kW]
Default value 460 kW Alternative config NO
Step 1 kW
Comm object 8633 Related applications MCB, MGCB
Description
This setpoint is used to adjust the load reserve for stop of next gen-set in absolute mode. i.e. #Power
Management Mode (page 192) = ABS.
IMPORTANT: Logical binary input LOAD RES 2 ACTIVE (PAGE 430) has to be activated,
otherwise setpoints of Load Reserve Set 1 are used.
Note: See Power management (page 78) chapter for more information.
#Stopping Load Reserve 2
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units]
0 .. #Stopping Rel Load Reserve 2 (page 197) [%]
Default value 60 % Alternative config NO
Step 1 %
Comm object 10649 Related applications MCB, MGCB
Description
This setpoint is used to adjust the load reserve for start of next gen-set in relative mode. i.e. #Power
Management Mode (page 192) = REL.
IMPORTANT: Logical binary input LOAD RES 2 ACTIVE (PAGE 430) has to be activated,
otherwise setpoints of Load Reserve Set 1 are used.
Note: See Power management (page 78) chapter for more information.
#Starting Rel Load Reserve 2
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals