InteliMains 210 Global Guide
196
Setpoint group Power Management Related FW 2.0.0
Range [units]
#Starting Load Reserve 2 (page 195) .. 32 000 [kW]
Default value 460 kW Alternative config NO
Step 1 kW
Comm object 8633 Related applications MCB, MGCB
Description
This setpoint is used to adjust the load reserve for stop of next gen-set in absolute mode. i.e. #Power
Management Mode (page 192) = ABS.
IMPORTANT: Logical binary input LOAD RES 2 ACTIVE (PAGE 430) has to be activated,
otherwise setpoints of Load Reserve Set 1 are used.
Note: See Power management (page 78) chapter for more information.
#Stopping Load Reserve 2
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units]
0 .. #Stopping Rel Load Reserve 2 (page 197) [%]
Default value 60 % Alternative config NO
Step 1 %
Comm object 10649 Related applications MCB, MGCB
Description
This setpoint is used to adjust the load reserve for start of next gen-set in relative mode. i.e. #Power
Management Mode (page 192) = REL.
IMPORTANT: Logical binary input LOAD RES 2 ACTIVE (PAGE 430) has to be activated,
otherwise setpoints of Load Reserve Set 1 are used.
Note: See Power management (page 78) chapter for more information.
#Starting Rel Load Reserve 2
6 back to List of setpoints