Subgroup: Start/Stop Timing
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 3 600 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8492 Related applications MCB, MGCB
Description
This setpoint adjusts the delay for starting the next gen-set after the reserve has dropped below the reserve
for start.
#Next Engine Start Delay
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 3 600 [s]
Default value 20 s Alternative config NO
Step 1 s
Comm object 8494 Related applications MCB, MGCB
Description
This setpoint adjusts the delay for stopping the gen-set after the reserve has risen above the reserve for
stop.
#Next Engine Stop Delay
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 600 [s]
Default value 60 s Alternative config NO
Step 1 s
Comm object 8495 Related applications MCB, MGCB
Description
This setpoint is used to adjust how long the particular gen-set will suppress it's own Slow stop alarm to give
chance to another gen-set to start and replace the defective one.
Note: If there isn't any available gen-set to start, the alarm is not suppressed.
Note: This function is not supported in BTB application.
#Slow Stop Delay
6 back to List of setpoints