InteliMains 210 Global Guide
199
Subgroup: Over Load Next Start Protection
Setpoint group Power Management Related FW 2.0.0
Range [units] Enabled / Disabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 14942 Related applications MCB, MGCB
Description
This setpoint is intended for activation of the protection against the overloading of the system due to rapid
change of the load. It makes the next gen-set (in priority order) to start when the load excises the value given
by the setpoint #Overload Next Start Level (page 199) right after the delay #Overload Next Start Delay (page
199).
#Overload Next Start Protection
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 100 [%]
Default value 80 % Alternative config NO
Step 1 %
Comm object 14941 Related applications MCB, MGCB
Description
Threshold level for #Overload Next Start Protection (page 199).
#Overload Next Start Level
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 5 [s]
Default value 1 s Alternative config NO
Step 1 s
Comm object 8493 Related applications MINT
Description
Delay for #Overload Next Start Protection (page 199).
#Overload Next Start Delay
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals