InteliMains 210 Global Guide
200
Subgroup: Run Hours Equalization
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 65 000 [h]
Default value 100 h Alternative config NO
Step 1 h
Comm object 9919 Related applications MCB, MGCB
Description
This setpoint adjusts the "dead-band" for the running hours equalization function (#Priority Auto Swap (page
192) = Run Hours Equal). The priorities are swapped not until the relative engine hours difference is higher
than this dead-band.
#Run Hours Max Difference
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 0,0 .. 200000,0 [h]
Default value 0,0 h Alternative config NO
Step 0,1 h
Comm object 10600 Related applications MINT
Description
Running hours base corrects actual Running hours differences between particular gen-sets.
Example:
Gen-set 1 actual Running hours = 1000 h.
Gen-set 2 actual Running hours = 2000 h.
Adjust this setpoint for Gen-set 1 = 1000 h and for Gen-set 2 = 2000 h to be on the same base for
Running Hours Equalization.
Note: This function is not supported in BTB application.
Run Hours Base
6 back to List of setpoints
Subgroup: Efficient Mode
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 3 600 [s]
Default value 10 s Alternative config NO
Step [s]
Comm object 8896 Related applications MCB, MGCB
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand rose above the
upper limit of the current power band. Setpoint is taken into account only if #Priority Auto Swap (page 192) =
Efficient.
#Power Band Change Up Delay
6 back to List of setpoints