InteliMains 210 Global Guide
201
Setpoint group Power Management Related FW 2.0.0
Range [units] 0 .. 3 600 [s]
Default value 10 s Alternative config NO
Step [s]
Comm object 10795 Related applications MCB, MGCB
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand drops below the
lower limit of the current power band. Setpoint is taken into account only if #Priority Auto Swap (page 192) =
Efficient.
#Power Band Change Down Delay
6 back to List of setpoints
Subgroup: Group Settings
Setpoint group Power Management Related FW 2.0.0
Range [units] 1,2 .. 32 [-]
Default value 1 s Alternative config NO
Step 1 s
Comm object 10589 Related applications MCB, MGCB
Description
This setpoint selects the control group (to get more information on this function please refer to the chapter
Control groups (page 95) to which the particular gen-set belongs. If there aren't logical groups at the site,
adjust the setpoint to 1.
Note: This function is not supported in BTB application.
Control Group
6 back to List of setpoints
Setpoint group Power Management Related FW 2.0.0
Range [units] 1,2 .. 32 [-]
Default value 1 s Alternative config NO
Step 1 s
Comm object 10590 Related applications MCB, MGCB
Description
If the input GROUP LINK (PAGE 429) of this particular controller is used to provide the "group link" information
for two Control groups (to get more information refer to the chapter Control groups (page 95)), then this
setpoint is used to select which group is located at the left side of the group link breaker (bus tie breaker). If
this particular controller is not used for the group link function, adjust this setpoint to 1.
Group Link L
6 back to List of setpoints