LBI: G
Related FW 2.0.0 Related applications MCB, MGCB
Comm object 59
Description
This input is used for logical connection and disconnection of two gen-set groups selected with setpoints
Group Link L (page 201) and Group Link R (page 202). If the input is active, then the two selected groups will
perform power management, load sharing and kVAr sharing together as one large group.
Note: This function is independent on the group which the particular controller belongs to, i.e. the
controller can provide linking function e.g. for groups 3,4 although it belongs to group 2.
Note: This function is not supported in BTB application.
Group link
6 back to Logical binary inputs alphabetically
LBI: H
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 192
Description
Binary input has the same function as Horn reset button on the InteliMains 210 front panel.
Horn Reset Button
6 back to Logical binary inputs alphabetically
LBI: L
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 107
Description
Use this binary input with binary input LANG SELECTION 2 (PAGE 430) to choose required language of
controller. The system is based on binary numbers.
Binary input Binary number Active language
Language Selection 1 is active 1 First language (English)
LANG SELECTION 2 (PAGE 430) is active 2 Second language
Language Selection 1 and LANG SELECTION
2 (PAGE 430) are active
3 Third language
Lang Selection 1
6 back to Logical binary inputs alphabetically