InteliMains 210 Global Guide
206
Setpoint group Synchronisation Related FW 2.0.0
Range [units] 0,01 .. 0,50 [Hz]
Default value 0,15 Hz Alternative config NO
Step 0,01 Hz
Comm object 14799 Related applications MCB, MGCB, BTB
Description
Window of slip frequency for slip synchronization (Synchronization Type (page 204) = Slip Synchro).
Slip Frequency Window
6 back to List of setpoints
Setpoint group Synchronisation Related FW 2.0.0
Range [units] 20 .. 1 000 [ms]
Default value 80 ms Alternative config NO
Step 1 ms
Comm object 14800 Related applications MCB, MGCB, BTB
Description
Latency of MGCB.
IMPORTANT: This setpoint is enable, when Synchronization Type (page 204) has Split Synchro
value
MGCB Latency
6 back to List of setpoints
Setpoint group Synchronisation Related FW 2.0.0
Range [units] 20 .. 1 000 [ms]
Default value 80 ms Alternative config NO
Step 1 ms
Comm object 14801 Related applications MCB, MGCB, BTB
Description
Latency of MCB.
IMPORTANT: This setpoint is enable, when Synchronization Type (page 204) has Split Synchro
value
MCB Latency
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals