InteliMains 210 Global Guide
264
Setpoint group CM-RS232-485 Related FW 2.0.0
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Alternative config NO
Step [-]
Comm object 24477 Related applications MCB, MGCB, BTB
Description
If the MODBUS mode is selected on COM1 channel, the MODBUS communication speed can be adjusted
here.
COM1 MODBUS Communication Speed
6 List of setpoints (page 165)
Setpoint group CM-RS232-485 Related FW 2.0.0
Range [units] Direct / MODBUS [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24451 Related applications MCB, MGCB, BTB
Description
Communication protocol switch for the COM2 channel.
Direct InteliConfig communication protocol via serial cable.
MODBUS MODBUS protocol.
COM2 Mode
6 back to List of setpoints
Setpoint group CM-RS232-485 Related FW 2.0.0
Range [units] 9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value 57600 bps Alternative config NO
Step [-]
Comm object 24340 Related applications MCB, MGCB, BTB
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line can
be adjusted here. Speed of second part of line has to be adjusted to the same value.
Note: Winscope supports only 19200, 38400, 57600 speeds.
COM2 Communication Speed
6 List of setpoints (page 165)