InteliMains 210 Global Guide
431
LBI: N
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 184
Description
Binary input has no function. Use this configuration when binary input is not used.
Not Used
6 back to Logical binary inputs alphabetically
LBI: R
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 620
Description
The controller is switched to the AUTO mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / TEST binary inputs
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote AUTO
6 back to Logical binary inputs alphabetically
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 4
Description
If the input is active, the controller will not accept any actions regarding the system control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote CtrlLock
6 back to Logical binary inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals