InteliMains 210 Global Guide
457
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 48
Description
The output is intended for control of undervoltage coil of bus circuit breaker. The output is active the whole
time when the controller is switched on. The output is deactivated for at least 5 seconds in the moment the
breaker has to be switched off.
Image 8.142 BTB UV Coil close command
Image 8.143 BTB UV Coil open command
BTB UV Coil