InteliMains 210 Global Guide
458
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 77
Description
This output is active when the Bus Right voltage and frequency is within limits.
Bus Right Healthy
6 back to Logical binary outputs alphabetically
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 78
Description
This output is active while Bus Left failure is not detected and Bus Left voltage and frequency is within limits.
Bus Left Healthy
6 back to Logical binary outputs alphabetically
LBO: E
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 1250
Description
This is an output from the Exercise timer 1. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 1 (page 249) subgroup. This output is
active when Timer 1 is active.
Note: In the event that both Timers are active at the same time, Subgroup: Timer 1 (page 249) has a
higher priority than Subgroup: Timer 2 (page 256).
Exercise Timer 1
6 back to Logical binary outputs alphabetically
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 1251
Description
This is an output from the Exercise timer 2. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 2 (page 256) subgroup. This output is
active when Timer 2 is active.
Note: In the event that both Timers are active at the same time, Subgroup: Timer 1 (page 249) has a
higher priority than Subgroup: Timer 2 (page 256).
Exercise Timer 2
6 back to Logical binary outputs alphabetically