InteliMains 210 Global Guide
517
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right frequency. The following setpoints are related
to it:
Bus Right Overfrequency (page 184)
Bus Right < > Frequency Delay (page 184)
Bus Right Overfrequency
6 back to List of alarms level 2
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right frequency. The following setpoints are related
to it:
Bus Right Underfrequency (page 184)
Bus Right < > Frequency Delay (page 184)
Bus Right Underfrequency
6 back to List of alarms level 2
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right phase voltage unbalance. The following
setpoints are related to it:
Bus Right Voltage Unbalance (page 183)
Bus Right Voltage Unbalance Delay (page 183)
Bus Right Voltage Unbalance
6 back to List of alarms level 2
Alarm Type Other
Alarmlist message EM(A) - a message lost
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(A) - a message lost
6 back to List of alarms level 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals