Ruckus ICX 7450 Switch Hardware Installation Guide 35
Part Number: 53-1003899-09
FIGURE 24 Attaching the rear brackets to the rack posts
Flush-rear (recessed) mounting the device in the rack
The flush-rear (recessed) mounting is similar to the flush-front mounting except that the brackets are reversed on the device.
The illustrations in the rack installation procedures show a 1U device, but the instructions are the same for a 1.5U or 2U device.
The illustrations in the rack installation procedures are for reference only and may not show the actual device.
Complete the following tasks to install the device in a four-post rack:
1. “Attaching the front brackets to the rear of the device” on page 36
2. “Attaching the extensions to the front of the device” on page 36
3. “Installing the device in the rack” on page 37
4. “Attaching the rear brackets to the extensions at the front of the device” on page 38
5. “Attaching the rear brackets to the front rack posts” on page 39
1 Screws, 10-32 x 5/8-in., panhead Phillips 2 Retainer nuts, 10-32
The device must be turned off and disconnected from the fabric during this procedure.