Condair EL2
– System 3: Supply air humidity control with continuous output limitation
Supply air humidity control (humidity sensor installed in supply air duct) should be used
only where room humidity control is impracticable for technical reasons. Such systems
always require a PI-controller.
Thehumiditysensor(A1)islocatedinthesupplyairductafterthesteamdistributionpipe.The
humiditysensor(A2)forthecontinuousoutputlimitationislocatedinthesupplyairductbefore
the steam distribution pipe. Such a system requires a PI-controller with the option to connect a
second humidity sensor.
A1/2 humidity sensor
B1 ventilation interlock
B2 airowmonitor
B3 safetyhumidistat
PI
E
External PI controller
Y inputsignalfromA1
Z inputsignalfromA2
Which humidity control system for which application?
Application Location of the humidity sensor
room or exhaust air duct supply air duct
Airconditioningsystemswith:
–supplyairportionupto33% System 1 System 1
–supplyairportionupto66% System 1 or 2 System 2 or 3
–supplyairportionupto100% System 2 System 3
– supply air humidity control — System 3
Directroomhumidication System 1 —
Please contact your Condair supplier, if your application meets the following conditions:
– Humidicationofsmallroomsupto200m
3
– Airconditioningsystemswithahighnumberofairexchanges
– Systemswithvariableairvolumeow
– Testfacilitieswithextremecontrolaccuracyrequirements
– Rooms with a high variation in max. steam capacity
– Systemswithtemperatureuctuations
– Coldroomsandsystemswithdehumidication
Admissible input signals
– 0...10VDC(externalcontinuouscontroller)
– 24VOn/Off(humidistat)