EasyManua.ls Logo

Condair EL2 - Installing the Condensate Hose

Condair EL2
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
– Steamhosesmustbepreventedfromsagging(condensatepockets);ifnecessary,supportwith
pipe clamps, trough, or wall brackets, or install a condensate drain in the steam hose.
Important!Whendecidingonthelengthandlayoutofthehose,itshouldbenotedthatthesteam
hose may become somewhat shorter with progressive ageing.
Securing the hose
Thesteamhosemustbesecuredtothesteamdistributionpipeandhumidiersteamoutletbymeans
ofhose clamps.
Caution!Donotovertightenthehoseclamponthesteamconnectorofthesteamhumidier.
Steamlinewithxedpiping
Forsteamlineswithxedpiping,thesameinstructionsapplytothelayingofthepipingasalready
described.Thefollowingadditionalnotesshouldbeobserved:
The minimum internal diameter of 30 mm or 45 mm respectively should be applied over the
wholelengthofthe
piping.
–
UseexclusivelyCupipeorstainlesssteel(min.DIN1.4301).
– Tominimizethecondensateformation(=loss),thesteampipesmustbeinsulated.
The minimum bend radiusforsolidpipesis4-5 x internal diameter.
– Connectionofthesteampipestothesteamdistributionpipeandsteamhumidieriseffected
bymeansofshortlengthsofsteamhosesecuredwithhoseclamps.Connectiontothesteam
humidierissecuredviaaG2”coupling.
Important! Allowancemustbemadeforapressure loss of 10 mm water column (approx.
100 Pa) per meter length or per 90° bend.
5.4.6 Installing the condensate hose
Important! Use original Condair condensate hose exclusively. Other types ofhoses can cause
operationalmalfunctions.
Thehoselayoutdependsonthepositionofthesteamdistributionpipe:
Steam distribution pipe is mounted morethan300mmabovethetopedgeofthehumidier:
Condensatehoseisleddowntothehumidierwithaminimum slope of 20 %,intheformof
a siphon (min. hose bend diameter Ø200 mm ),andinsertedabout2cmintothespecied
opening.
min. 300 mm
min. 20 %
Ømin. 200 mm
min. 300 mm
min. 20 %
Ømin. 200 mm