5.6.4 Inserting the EL2 Card
All important operating parameters such as the maximum steam capacity and the heating voltage
are permanently stored on the EL2 Card.
Beforeyoustarttheelectricalinstallation,check whether the EL2 Card is installed.Ifitisnot,
check whether the type designation on the EL2 Card supplied corresponds with the type
designation on the data plate inside the unit.Ifthedesignationsmatch,placetheEL2Cardin
the card holder on control print . Then cover the data plate above the type plate inside the unit with
thedataplatesupplied(self-adhesive).
IfthetypedesignationontheEL2Cardandthedataplatedonotmatch,theEL2Cardmustnotbe
installed.Ifthisisthecase,contactyourCondairsupplier.
5.6.5 Inspecting the electrical installation
Checkthefollowingpoints:
Dothesupplyvoltagesforheatingandcontrolcomplywiththerelevantvoltagesgiveninthe
wiringdiagram?
IsthecorrectEL2Cardinserted?
Arethevoltagesupplies(heatingandcontrolvoltage)correctlyfused?
Istheserviceswitch“Q..”installedinthesupplylinefortotheheatingandcontrolvoltage?
Areallcomponentscorrectlyconnectedaccordingtothewiringdiagram?
Areallconnectingcablesfastened?
Aretheconnectingcablesfreeoftension(passedthroughcableglands?)
Doestheelectricinstallationmeettheapplicablelocalregulationsforelectricinstallations?
Isthefrontpanelmountedandcorrectlyxedwiththetwoscrews?