Generalsettings(“Settings”)
WiththeDIPswitches“Settings”youcansetdifferentunitparameters.Theunitparametersarepreset
inthefactoryandmayonlybemodiedbytheclientafterconsultingtheCondairrepresentative.
Switch Factory setting Description
1 OFF ON:lowwaterconductivity <125 µS/cm
OFF:normalwaterconductivity≥125µS/cm
2 OFF ON:standbydraining(72hours) activated
OFF:standbydraining(72hours) deactivated
3 OFF ON:forceddraining(72hours) activated
OFF:forceddraining(72hours) deactivated
4 OFF ON:cleanablesteamcylinder
OFF:replaceablesteamcylinder
5 ON ON:theheatingvoltageisinterruptedduringdrainingofthesteam
cylinder
OFF:theheatingvoltageisinterruptedduringdrainingandrelling
ofthesteamcylinder
6 OFF ON:Offsetcontrolsignalactivated(2-10V)
OFF:Offsetcontrolsignaldeactivated(0-10V)