EasyManua.ls Logo

Condair EL2 - Unit Configuration

Condair EL2
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
Control signal
External continuous humidity controller 0-10V (A1)
Anexternalhumiditycontinuouscontrolleristobeconnectedtothecontacts“IN”(+)and“GND”
(–)oftheterminalblock“X1”.
24 VDC On/Off humidistat (passive)
An24VDCOn/Offhumidistatistobeconnectedtothecontacts“V+”and“IN”oftheterminal
block “X1”.
Note:forthe24VDCOn/Offcontrolajumpermustbeseton“JP1”.
230V On/Off control (active)
Thesignallineofa230VOn/Offcontrolistobeconnectedtothecontact“VD”oftheterminal
block“X2”viaexternalfuse“F4”(max.10A,slow-acting).
Connecting the fan unit FAN3 EL2
Refertotheseparatedocumentationofthefanunit.
5.6.3 Unitconguration
Allsettingcomponentsfortheunitcongrationarelocatedonthecontrolboard:
– Rotaryswitch“Cylinder”: cylindertype
– Potentiometer“DrainFactor”: drainfactor
– Potentiometer“PowerLimit”: powerlimitation
– DIPswitch“Settings”: generalsettings
Settingthesteamcylindertype(“Cylinder”)
Usetherotaryswitch“Cylinder”toselectthetypeofsteamcylinderused.
Position 0 1 2 3 4 5 6 7 8 9 A B
Cylinder type 342 343 344 363 444 464 544 564 654 674 644 664
Setting the drain factor
Usethepotentiometer“DrainFactor”tosetthedrainfactor(settingrange:0.5...2.0,factorysetting:
1.0).
Setting the power limitation
Usethepotentiometer“PowerLimit”tosetthepowerlimitationin%ofthemaximumcapacity(setting
range:30...100%,factorysetting:100%).

Table of Contents

Related product manuals