8.2 Malfunction lists
8.2.1 System faults
Warning Error Cause Remedy
Code Malfunction Code Malfunction
E1 EL2 Card missing No EL2 Card installed on the
control board.
Install EL2 Card or start test run.
––– ––– E2 EL2 Card is empty No data stored on the EL2 Card. Install new EL2 Card.
––– ––– E2 EL2 Card is
defective
Invalid data stored on the EL2
Card.
Install new EL2 Card.
––– ––– E2 EL2 Card is
incompatible
The installed EL2 Card is not com-
patible with the hardware of the
unitorwiththebasicsettingsofthe
control electronics.
Install correct EL2 Card. Let your
Condair service technician adjust
the basic settings.
––– ––– E10 Hardware fault Controlboarddefective. Replace control board.
8.2.2 Unit faults
Warning Error Cause Remedy
Code Malfunction Code Malfunction
W20 External safety
chain is open
––– ––– Ventilationinterlockopen. Ifapplicable,check/turnonventi-
lation system.
Airowmonitortriggered. Checkventilator/lteroftheventi-
lation system.
Safetyhumidistattriggered. Wait.Ifapplicable,checksafety
humidistat
W21 Max.llinglevelof
steam cylinder
reached
E21 Max.llinglevelof
steam cylinder
reached but
no heating current
Water conductivity too low (after
initialoperation).
Waituntilthemineralcontentofthe
cylinder has increased
Waterconductivitytoolowfortype
ofsteamcylinder.
Select correct steam cylinder
type.
Phasefailureheatingvoltage. Check service switch in the mains
supply line and switch on if ap-
plicable.Checkmainsfuse(s)and
replaceifapplicable.
W22 Permissiblelling
time exceeded (20
minutes)
E22 Permissiblelling
time exceeded (more
than 4 hours)
Water supply obstructed/shut-off
valve closed/water pressure too
low.
Inspect water supply (lter, water
piping, etc.), check/open shut-off
valve, check water pressure.
Inletvalveblockedordefective. Inspect strainer insert in the inlet
valve,ifapplicablecleanstrainer
insert or replace inlet valve.
Excessive back pressure in the
steam line (duct pressure too high,
steamlinetoolongorkinked),caus-
ingwaterlossviallingcup.
Check duct pressure, inspect steam
installation. If applicable install
pressure compensation kit (see
options).
Leakage in the water system. Inspectwatersystemandsealif
necessary.