EasyManua.ls Logo

Cornelius VIPER - Page 55

Cornelius VIPER
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Viper Low overrun Service Manual
© 2016, Cornelius Inc - 49 - Publication Number: 621360241LOEWSE
Figure 40. Side View of CO2 Pulse Valves
Figure 41. Front View of CO
2 Pulse Valves
SYRUP AND WATER SHUTOFF SOLENOID REPLACEMENT
The syrup and water shutoff valves and solenoids are mounted on a single bracket, as shown in Figure 42. Perform
the procedure in Table 52 to replace the valves.
Table 51.
Step Action
1 Disconnect power from the unit.
2 Disconnect the CO
2 supply from the unit.
3 Remove the rear cover and side panels.
4 Carefully remove the tubing from the rear of the valve.
5 Remove the mounting tie-wrap from the rear of the valve.
6 Replace the valve.
7 Reverse the procedure to reinstall the valve into the unit.
8 Test the unit for CO
2 leaks.
9 Replace the rear and side panels.
10 Reconnect power to the unit.
Pulse Valve
(1
OF 3)
Mounting
Tie-Wrap
Pulse Valves

Other manuals for Cornelius VIPER

Related product manuals