95
Table 6-6 HVRT Parameters (IEEE5147, Rule21, and ISO-NE)
HVRT
Setting Range
Parameter
Name
Description
IEEE1547 Rule21 ISO-NE
Min Default Max Min Default
Max Min Default
Max
HVRTVolt
high voltage
st
nd
100
125
135
100
125
135
100
120
135
HVRTTime
Time of Level high voltage
st
nd
0
0
655
0
0
655
0
0
655
HVRTVolt
high voltage
rd
th
100
124
135
100
120
135
100
120
135
HVRTTime
Time of Level high voltage
rd
th
0
0.80
655
0
0.11
655
0
0.25
655
HVRTVolt
high voltage
th
th
100
115
135
0
110
135
0
117.5
135
HVRTTime
Time of Level high voltage
th
th
0
12.50
655
0
12.50
655
0
0.55
655
HVRTVolt
high voltage
th
th
100
115
135
100
110
135
100
115
135
HVRTTime
Time of Level high voltage
th
th
0
12.50
655
0
12.50
655
0
10.50
655